F0 on a Gree air conditioner: low refrigerant (refrigerant protection)This is what you see on the indoor unit's display. Cooling weakens, then the unit stops to protect itself.
The unit went into protection mode because it sees the refrigerant is insufficient. Gree says most F0 cases are caused by the refrigerant amount: either the extra charge needed for long pipes wasn't added at installation, or there is a leak.
then restore it once. If F0 returns, the problem is real.
Safe for youShortly after installation? Most likely the extra refrigerant for the pipe length wasn't added. After years? Most likely a leak.
Safe for youOily spots around the nuts on both units usually point to the leak. Don't touch them.
Safe for youRunning repeatedly with low refrigerant strains the compressor.
Safe for youRecharging refrigerant and leak testing need tools and a licence. Don't attempt it yourself.
The extra amount required for the pipe length wasn't added. Gree lists this as the first cause.
Most likely if the code appeared after years of the unit working well.
Gives a wrong reading, so the unit thinks the refrigerant is low.
Less common; the technician checks it after the above.
My Gree air conditioner shows code F0. I disconnected the power for 10 minutes and the code came back. I want the refrigerant pressure measured and the leak found and repaired, not just a recharge.
Gree advises the technician to leak-test with nitrogen, then evacuate and charge by weight. Recharging without a repair means the code will come back.
No. If there is a leak, the code will return within weeks. The leak must be found and fixed first.
No, almost the opposite: E1 is high pressure, F0 is low refrigerant.
Yes, a faulty evaporator temperature sensor can give F0 with a full charge. The technician measures it with a meter.