U4 on a Daikin air conditioner: communication fault between the unitsThis is what you see on the remote or the unit's display. The unit stops, and the code often appears a few minutes after switching on.
The indoor unit sends a signal to the outdoor unit and waits for a reply. When no valid reply arrives for several minutes, it shows U4. In most cases the cause is the connecting wire or its terminals, not a damaged board.
Turn the power off at the breaker and back on. If the code was caused by a short power cut, it will clear. Repeating it over and over doesn't help and strains the inverter's capacitors.
Safe for youThe outdoor unit's breaker may be off or half-tripped, so the indoor unit keeps running and shows U4.
Safe for youA thunderstorm, a power cut, electrical work in the house, or a new installation? Tell the technician.
Safe for youThe terminals carry dangerous voltage, even shortly after the power is turned off.
Safe for youIf U4 returns after one restart, it is a real fault and needs a technician.
The communication line between the units is sensitive to the order of the two wires. By far the most common cause.
Cut or crushed at the cable clamps, or a thin wire not meant for communication over long distances.
Its breaker is off or its fuse blown, while the indoor unit runs.
Damages the communication circuit on one of the boards; other codes often appear with it.
The last thing to suspect after checking the power and wiring.
My Daikin air conditioner shows code U4. I restarted it once and the code came back, and the outdoor unit has power. I want the communication wire, its terminals and their order in both units checked before any board is replaced.
The technician can measure the voltage on the communication line to tell which unit is the problem, without swapping boards by trial and error.
No. A short power cut can cause a temporary U4. If the fault is real, it will come back within minutes of running.
Heat can damage the communication cable's insulation if it is wrapped together with the hot refrigerant pipes, so the fault shows up in hot weather and disappears in the cold.
No. It is a communication fault. Compressor faults have other codes, usually starting with the letter L.