Code U4 on a Daikin air conditioner: communication fault between the units

This is what you see on the remote or the unit's display. The unit stops, and the code often appears a few minutes after switching on.

Short answer

The indoor unit sends a signal to the outdoor unit and waits for a reply. When no valid reply arrives for several minutes, it shows U4. In most cases the cause is the connecting wire or its terminals, not a damaged board.

Is it dangerous?
No, but the unit is stopped
Does it clear by itself?
If it was temporary after a power cut
Can I fix it myself?
The first steps only

What to do now, in order

  1. Switch off and on just once

    Turn the power off at the breaker and back on. If the code was caused by a short power cut, it will clear. Repeating it over and over doesn't help and strains the inverter's capacitors.

    Safe for you
  2. Make sure both units have power

    The outdoor unit's breaker may be off or half-tripped, so the indoor unit keeps running and shows U4.

    Safe for you
  3. Remember what came before the code

    A thunderstorm, a power cut, electrical work in the house, or a new installation? Tell the technician.

    Safe for you
  4. Don't open any cover

    The terminals carry dangerous voltage, even shortly after the power is turned off.

    Safe for you

If U4 returns after one restart, it is a real fault and needs a technician.

Causes, from most to least likely

Loose terminals or reversed wires

Most common

The communication line between the units is sensitive to the order of the two wires. By far the most common cause.

Damaged or unsuitable wire

Cut or crushed at the cable clamps, or a thin wire not meant for communication over long distances.

Outdoor unit has no power

Its breaker is off or its fuse blown, while the indoor unit runs.

Power surge or lightning

Damages the communication circuit on one of the boards; other codes often appear with it.

Damaged control board

The last thing to suspect after checking the power and wiring.

What to tell the technician

My Daikin air conditioner shows code U4. I restarted it once and the code came back, and the outdoor unit has power. I want the communication wire, its terminals and their order in both units checked before any board is replaced.

The technician can measure the voltage on the communication line to tell which unit is the problem, without swapping boards by trial and error.

Frequently asked questions

U4 appeared after a power cut and then went away. Should I worry?

No. A short power cut can cause a temporary U4. If the fault is real, it will come back within minutes of running.

Why does the code only appear in summer?

Heat can damage the communication cable's insulation if it is wrapped together with the hot refrigerant pipes, so the fault shows up in hot weather and disappears in the cold.

Does U4 mean a compressor fault?

No. It is a communication fault. Compressor faults have other codes, usually starting with the letter L.