E1 on a Gree air conditioner: high-pressure protectionThis is what you see on the indoor unit's display. The unit stops, often at the hottest time of the afternoon.
The pressure in the refrigerant circuit rose above the safe limit, so the unit stopped the compressor. Usually the outdoor unit isn't getting rid of heat well: a dirty condenser, a fan that isn't turning, or things blocking the air around it.
at the breaker, especially before touching the outdoor unit.
Safe for youLeaves, bags, stored items, or a wall too close. Leave about 30 cm at the sides and 60 cm in front of the fan.
Safe for youGently remove dust from the outdoor unit's fins without bending them; ideally rinse them with water from the inside out. Clean the indoor unit's filters too.
Safe for youIn cooling mode it should reach full speed within half a minute. If it hums without turning, the run capacitor is usually faulty. Keep your hands away from the blades.
Safe for youIf E1 comes back after cleaning and the fan is working, don't keep restarting. Checking the refrigerant and pressure needs a refrigeration technician with gauges.
The most common, especially in summer and in dusty areas.
Its motor or run capacitor is faulty.
Usually after an inaccurate recharge. Needs measuring with gauges.
A bent or crushed pipe, or a service valve left half-closed after installation.
After ruling out the above.
My Gree air conditioner shows code E1. I cleaned the outdoor condenser and the filters, the outdoor fan is turning, and the code came back. I want the refrigerant pressure and charge and the high-pressure switch checked.
If the unit was recently recharged with refrigerant, mention it, because overcharging is a known cause of this code.
Because high outdoor temperatures raise the pressure, so any weakness in cooling the outdoor unit shows up at peak time.
No, usually the opposite. Low refrigerant has another code on Gree units: F0.
No. A strong jet bends the fins. Use a gentle spray with the power off.