A3tali

Home ‹ Generators ‹ Smartgen

Smartgen generator error codes

26 codes, each with what it means, what you can safely try yourself, and when to call a technician. Alarms from controllers common on diesel generators.

11 of the 26 entries on this page come from a single unconfirmed source, so they are listed separately at the end of the page.

A code's meaning can differ between models of the same brand. Check what you find here against your appliance's manual before any repair.

Quick table

CodeMeaningWho handles it
Fail to StartFailed to start after crank attemptsTry it yourself first
Emergency StopEmergency stop signal activeTry it yourself first
Low Oil PressureOil pressure below the limitNeeds a technician
High Water TempCoolant temperature highNeeds a technician
Gen Over VoltageGenerator voltage above the limitNeeds a technician
Gen Under VoltageGenerator voltage below the limitNeeds a technician
Gen Over SpeedGenerator speed above the limitNeeds a technician
Gen Under SpeedGenerator speed below the limitNeeds a technician
Loss of Speed SignalSpeed sensor signal lostNeeds a technician
Charge Alt FailThe charging alternator isn't charging the batteryNeeds a technician
Battery Over VoltageBattery voltage highNeeds a technician
Battery Under VoltageBattery voltage lowTry it yourself first
Over CurrentLoad current above the limitNeeds a technician
Low Fuel LevelFuel level lowTry it yourself first
Fail to StopThe engine didn't stop after the stop commandNeeds a technician
Over Freq ShutdownFrequency high, protective shutdownNeeds a technician
Under Freq ShutdownFrequency low, protective shutdownTry it yourself first
Genset FailedThe generator isn't producing powerNeeds a technician
Low Coolant LevelCoolant level lowTry it yourself first
Temp Sensor OpenCoolant temperature sensor not connectedTry it yourself first
Oil Pressure Sensor OpenOil pressure sensor not connectedTry it yourself first
Maintenance WarningScheduled maintenance dueNot a fault
Over PowerPower drawn higher than the settingTry it yourself first
ECU WarnWarning from the engine computerNeeds a technician
ECU ShutdownShutdown from the engine computerNeeds a technician
ECU FailNo data from the engine computerNeeds a technician

Every code explained

Don't open the radiator cap while the engine is hot, as pressurised steam burns; don't go near a running generator in loose clothing, and keep children away from it.

Fail to Start Failed to start after crank attempts Try it yourself first

What it means
A problem with the starting battery or its charging circuit.
What the source says
Weak battery or fuel not arriving
What you can do
Check the battery terminals: clean off corrosion and tighten the connections, and measure the voltage if you can. Try an external charger or another battery, and make sure fuel is arriving.
When to call a technician
If the battery is sound and charged. The charging alternator, the starter motor or their wiring is checked.

Emergency Stop Emergency stop signal active Try it yourself first

What it means
The emergency stop button is pressed or its circuit is active, so the generator is stopped and won't start.
What the source says
Emergency stop pressed or its input active
What you can do
Release the button by twisting it in the direction marked on it, then press Reset on the controller and restart.
When to call a technician
If the button is released and the alarm stays. The button's circuit or wiring needs checking.

Low Oil Pressure Oil pressure below the limit Needs a technician

What it means
Engine oil pressure is below the safe limit, and running with it destroys the engine.
What the source says
Low oil or a sensor fault
What you can do
Stop the generator immediately. Check the oil level with the dipstick when the engine is cold, add the right type if it is low, and look for a leak under the engine.
When to call a technician
If the level is normal and the alarm stays. The pressure sensor or the oil pump is checked.

High Water Temp Coolant temperature high Needs a technician

What it means
The engine temperature exceeded the safe limit.
What the source says
Low coolant, a dirty radiator, or an overload
What you can do
Stop the generator and let it cool; don't open the radiator cap while it is hot. Once cool: check the coolant level, clean the dust off the radiator fins, and make sure the load isn't greater than the generator's capacity.
When to call a technician
If it keeps happening with full coolant and a clean radiator. The thermostat, water pump or temperature sensor is checked.

Gen Over Voltage Generator voltage above the limit Needs a technician

What it means
The generator's output is outside the allowed limits, or the load is larger than its capacity.
What the source says
A fault in the voltage regulator
What you can do
Disconnect some loads and restart. If it stabilises, the cause is an overload or an appliance with a high starting current.
When to call a technician
If the fault stays with a light load. The AVR voltage regulator or the alternator itself is checked.

Gen Under Voltage Generator voltage below the limit Needs a technician

What it means
The generator's output is outside the allowed limits, or the load is larger than its capacity.
What the source says
The voltage regulator or an overload
What you can do
Disconnect some loads and restart. If it stabilises, the cause is an overload or an appliance with a high starting current.
When to call a technician
If the fault stays with a light load. The AVR voltage regulator or the alternator itself is checked.

Gen Over Speed Generator speed above the limit Needs a technician

What it means
The engine speed is outside the allowed limit, so the power comes out at the wrong frequency.
What the source says
A fault in the speed governor
What you can do
Reduce the load to less than half the generator's capacity and try again, and make sure fuel is arriving plentifully.
When to call a technician
In most cases. The speed governor is adjusted or checked, which is a specialist's job.

Gen Under Speed Generator speed below the limit Needs a technician

What it means
The engine speed is outside the allowed limit, so the power comes out at the wrong frequency.
What the source says
Low fuel or an overload
What you can do
Reduce the load to less than half the generator's capacity and try again, and make sure fuel is arriving plentifully.
When to call a technician
In most cases. The speed governor is adjusted or checked, which is a specialist's job.

Loss of Speed Signal Speed sensor signal lost Needs a technician

What it means
A sensor or its circuit is giving the controller an illogical reading.
What the source says
The sensor, its wire, or its distance from the gear
What you can do
Visually check the visible sensor connections: has a wire come off or a plug loosened?
When to call a technician
In most cases. The sensor is measured and its wire checked.

Charge Alt Fail The charging alternator isn't charging the battery Needs a technician

What it means
A problem with the starting battery or its charging circuit.
What the source says
The alternator, its belt, or its wiring
What you can do
Check the battery terminals: clean off corrosion and tighten the connections, and measure the voltage if you can. Try an external charger or another battery, and make sure fuel is arriving.
When to call a technician
If the battery is sound and charged. The charging alternator, the starter motor or their wiring is checked.

Battery Over Voltage Battery voltage high Needs a technician

What it means
A problem with the starting battery or its charging circuit.
What the source says
A fault in the charging alternator or its regulator
What you can do
Check the battery terminals: clean off corrosion and tighten the connections, and measure the voltage if you can. Try an external charger or another battery, and make sure fuel is arriving.
When to call a technician
If the battery is sound and charged. The charging alternator, the starter motor or their wiring is checked.

Battery Under Voltage Battery voltage low Try it yourself first

What it means
A problem with the starting battery or its charging circuit.
What the source says
Weak battery or charging not reaching it
What you can do
Check the battery terminals: clean off corrosion and tighten the connections, and measure the voltage if you can. Try an external charger or another battery, and make sure fuel is arriving.
When to call a technician
If the battery is sound and charged. The charging alternator, the starter motor or their wiring is checked.

Over Current Load current above the limit Needs a technician

What it means
The generator's output is outside the allowed limits, or the load is larger than its capacity.
What the source says
Overload or a short in the circuit
What you can do
Disconnect some loads and restart. If it stabilises, the cause is an overload or an appliance with a high starting current.
When to call a technician
If the fault stays with a light load. The AVR voltage regulator or the alternator itself is checked.

Low Fuel Level Fuel level low Try it yourself first

What it means
Fuel isn't reaching the engine or is about to run out.
What the source says
The tank is nearly empty
What you can do
Check the fuel tank first, then the fuel tap and filter. After refuelling, bleed the air from the fuel system as the manual explains.
When to call a technician
If the tank is full and the alarm stays. The fuel pump or the level sensor is checked.

Fail to Stop The engine didn't stop after the stop command Needs a technician

What it means
The controller told the engine to stop but it didn't stop in the set time.
What the source says
The fuel shut-off valve or its circuit
What you can do
Nothing on your side except keeping away from the generator.
When to call a technician
Immediately. The fuel shut-off valve or its circuit has failed, which is dangerous.

Codes from a single source

We found the following in only one source, with no second source confirming it, so it is kept here apart from the confirmed explanations above. Treat it as a first hint and check it against your appliance's manual.

Over Freq Shutdown Frequency high, protective shutdown Needs a technician

What it means
The generator's frequency is above the set limit.
What you can do
Disconnect the loads and don't restart before it is checked.
When to call a technician
Straight away. The technician checks the governor and the speed setting.

Under Freq Shutdown Frequency low, protective shutdown Try it yourself first

What it means
The generator's frequency is below the limit, usually because of an overload or a fuel shortage.
What you can do
Reduce the loads, check the fuel and the filter, then switch off the generator, press Stop/Reset to clear the alarm, and restart.
When to call a technician
If it keeps happening with light loads.

Genset Failed The generator isn't producing power Needs a technician

What it means
The engine is running but the controller reads zero frequency.
What you can do
Switch off the generator, press Stop/Reset to clear the alarm, then restart.
When to call a technician
If it keeps happening. The technician checks the alternator, the voltage regulator and the sensing wires.

Low Coolant Level Coolant level low Try it yourself first

What it means
The coolant level sensor gave a signal.
What you can do
Switch off the generator and let it cool completely, then open the cap slowly and add coolant. Look for a leak.
When to call a technician
If the coolant drops again quickly.

Temp Sensor Open Coolant temperature sensor not connected Try it yourself first

What it means
The controller can't read the temperature sensor.
What you can do
Check the sensor's wire on the engine and make sure it is connected and not cut.
When to call a technician
If the wire is sound and the alarm stays.

Oil Pressure Sensor Open Oil pressure sensor not connected Try it yourself first

What it means
The controller can't read the oil pressure sensor.
What you can do
Check the sensor's wire on the engine and make sure it is connected and not cut.
When to call a technician
If the wire is sound and the alarm stays.

Maintenance Warning Scheduled maintenance due Not a fault

What it means
The generator's running hours have reached the set maintenance interval.
What you can do
Carry out the scheduled maintenance: oil and filters, then reset the maintenance counter from the controller.
When to call a technician
To do the maintenance if you don't do it yourself.

Over Power Power drawn higher than the setting Try it yourself first

What it means
The loads are drawing more power than the limit set in the controller.
What you can do
Reduce the loads, then switch off the generator, press Stop/Reset to clear the alarm, and restart.
When to call a technician
If it keeps happening with loads within the generator's capacity.

ECU Warn Warning from the engine computer Needs a technician

What it means
The engine's electronic control module sent a warning.
What you can do
Note any number or message that appears with it.
When to call a technician
It needs an engine diagnostic tool.

ECU Shutdown Shutdown from the engine computer Needs a technician

What it means
The engine control module stopped the generator.
What you can do
Note any number or message that appears with it, and don't keep restarting.
When to call a technician
Straight away. It needs an engine diagnostic tool.

ECU Fail No data from the engine computer Needs a technician

What it means
The controller isn't receiving any data from the engine control module.
What you can do
Make sure the communication cable between the panel and the engine is connected, then switch off the generator, press Stop/Reset to clear the alarm, and restart.
When to call a technician
If the alarm stays.

Sources