Home ‹ Generators ‹ Deep Sea DSE

Deep Sea (DSE) generator error codes

21 codes, each with what it means, what you can safely try yourself, and when to call a technician. Alarms from the British controllers such as the DSE 4520 and 6110, the most widespread in commercial generators.

6 of the 21 entries on this page come from a single unconfirmed source, so they are listed separately at the end of the page.

A code's meaning can differ between models of the same brand. Check what you find here against your appliance's manual before any repair.

Quick table

CodeMeaningWho handles it
Fail to StartFailed to start after several crank attemptsTry it yourself first
Emergency StopEmergency stop button pressedTry it yourself first
Low Oil PressureOil pressure below the safe limitNeeds a technician
High Coolant TempCoolant temperature highNeeds a technician
Charge Alternator FailThe battery charging alternator isn't chargingNeeds a technician
Over SpeedEngine speed exceeded the safe limitNeeds a technician
Under SpeedEngine speed lower than normalNeeds a technician
Fail to StopThe engine didn't stop after the stop commandNeeds a technician
Battery Low VoltageStarting battery voltage lowTry it yourself first
Battery High VoltageStarting battery voltage highNeeds a technician
Low Fuel LevelFuel level lowTry it yourself first
Gen Over VoltageGenerator output voltage above the limitNeeds a technician
Gen Under VoltageGenerator output voltage below the limitNeeds a technician
Over CurrentLoad current exceeded the allowed limitNeeds a technician
Maintenance DueScheduled maintenance dueTry it yourself first
CAN ECU Data FailNo data from the engine computerNeeds a technician
CAN ECU ShutdownShutdown from the engine computerNeeds a technician
Loss of Mag Pickup SignalNo signal from the speed sensorNeeds a technician
Over FrequencyFrequency highNeeds a technician
Under FrequencyFrequency lowTry it yourself first
Digital InputAlarm from an auxiliary inputTry it yourself first

Every code explained

Don't open the radiator cap while the engine is hot, as pressurised steam burns; don't go near a running generator in loose clothing, and keep children away from it.

Fail to Start Failed to start after several crank attempts Try it yourself first

What it means
A problem with the starting battery or its charging circuit.
What the source says
The battery is weak, fuel isn't arriving, or a starter motor fault
What you can do
Check the battery terminals: clean off corrosion and tighten the connections, and measure the voltage if you can. Try an external charger or another battery, and make sure fuel is arriving.
When to call a technician
If the battery is sound and charged. The charging alternator, the starter motor or their wiring is checked.

Emergency Stop Emergency stop button pressed Try it yourself first

What it means
The emergency stop button is pressed or its circuit is active, so the generator is stopped and won't start.
What the source says
The button itself is pressed or its circuit is open
What you can do
Release the button by twisting it in the direction marked on it, then press Reset on the controller and restart.
When to call a technician
If the button is released and the alarm stays. The button's circuit or wiring needs checking.

Low Oil Pressure Oil pressure below the safe limit Needs a technician

What it means
Engine oil pressure is below the safe limit, and running with it destroys the engine.
What the source says
Low oil, or a fault in the pressure sensor or the oil pump
What you can do
Stop the generator immediately. Check the oil level with the dipstick when the engine is cold, add the right type if it is low, and look for a leak under the engine.
When to call a technician
If the level is normal and the alarm stays. The pressure sensor or the oil pump is checked.

High Coolant Temp Coolant temperature high Needs a technician

What it means
The engine temperature exceeded the safe limit.
What the source says
Low coolant, a dirty radiator, or an overload
What you can do
Stop the generator and let it cool; don't open the radiator cap while it is hot. Once cool: check the coolant level, clean the dust off the radiator fins, and make sure the load isn't greater than the generator's capacity.
When to call a technician
If it keeps happening with full coolant and a clean radiator. The thermostat, water pump or temperature sensor is checked.

Charge Alternator Fail The battery charging alternator isn't charging Needs a technician

What it means
A problem with the starting battery or its charging circuit.
What the source says
The alternator belt, the alternator itself, or its wiring
What you can do
Check the battery terminals: clean off corrosion and tighten the connections, and measure the voltage if you can. Try an external charger or another battery, and make sure fuel is arriving.
When to call a technician
If the battery is sound and charged. The charging alternator, the starter motor or their wiring is checked.

Over Speed Engine speed exceeded the safe limit Needs a technician

What it means
The engine speed is outside the allowed limit, so the power comes out at the wrong frequency.
What the source says
A fault in the speed governor or the fuel
What you can do
Reduce the load to less than half the generator's capacity and try again, and make sure fuel is arriving plentifully.
When to call a technician
In most cases. The speed governor is adjusted or checked, which is a specialist's job.

Under Speed Engine speed lower than normal Needs a technician

What it means
The engine speed is outside the allowed limit, so the power comes out at the wrong frequency.
What the source says
Low fuel, a blocked filter, or an overload
What you can do
Reduce the load to less than half the generator's capacity and try again, and make sure fuel is arriving plentifully.
When to call a technician
In most cases. The speed governor is adjusted or checked, which is a specialist's job.

Fail to Stop The engine didn't stop after the stop command Needs a technician

What it means
The controller told the engine to stop but it didn't stop in the set time.
What the source says
The fuel shut-off valve or its circuit isn't working
What you can do
Nothing on your side except keeping away from the generator.
When to call a technician
Immediately. The fuel shut-off valve or its circuit has failed, which is dangerous.

Battery Low Voltage Starting battery voltage low Try it yourself first

What it means
A problem with the starting battery or its charging circuit.
What the source says
The battery is weak or charging isn't reaching it
What you can do
Check the battery terminals: clean off corrosion and tighten the connections, and measure the voltage if you can. Try an external charger or another battery, and make sure fuel is arriving.
When to call a technician
If the battery is sound and charged. The charging alternator, the starter motor or their wiring is checked.

Battery High Voltage Starting battery voltage high Needs a technician

What it means
A problem with the starting battery or its charging circuit.
What the source says
A fault in the charging alternator or its regulator
What you can do
Check the battery terminals: clean off corrosion and tighten the connections, and measure the voltage if you can. Try an external charger or another battery, and make sure fuel is arriving.
When to call a technician
If the battery is sound and charged. The charging alternator, the starter motor or their wiring is checked.

Low Fuel Level Fuel level low Try it yourself first

What it means
Fuel isn't reaching the engine or is about to run out.
What the source says
The tank is nearly empty, or the level sensor
What you can do
Check the fuel tank first, then the fuel tap and filter. After refuelling, bleed the air from the fuel system as the manual explains.
When to call a technician
If the tank is full and the alarm stays. The fuel pump or the level sensor is checked.

Gen Over Voltage Generator output voltage above the limit Needs a technician

What it means
The generator's output is outside the allowed limits, or the load is larger than its capacity.
What the source says
A fault in the AVR voltage regulator
What you can do
Disconnect some loads and restart. If it stabilises, the cause is an overload or an appliance with a high starting current.
When to call a technician
If the fault stays with a light load. The AVR voltage regulator or the alternator itself is checked.

Gen Under Voltage Generator output voltage below the limit Needs a technician

What it means
The generator's output is outside the allowed limits, or the load is larger than its capacity.
What the source says
The voltage regulator, low speed, or an overload
What you can do
Disconnect some loads and restart. If it stabilises, the cause is an overload or an appliance with a high starting current.
When to call a technician
If the fault stays with a light load. The AVR voltage regulator or the alternator itself is checked.

Over Current Load current exceeded the allowed limit Needs a technician

What it means
The generator's output is outside the allowed limits, or the load is larger than its capacity.
What the source says
A load greater than the generator's capacity, or a short in the circuit
What you can do
Disconnect some loads and restart. If it stabilises, the cause is an overload or an appliance with a high starting current.
When to call a technician
If the fault stays with a light load. The AVR voltage regulator or the alternator itself is checked.

Maintenance Due Scheduled maintenance due Try it yourself first

What it means
A reminder that scheduled maintenance is due after a set number of running hours, not a fault.
What the source says
A reminder set to a number of running hours
What you can do
Carry out the scheduled maintenance of oil and filters, then reset the reminder from the controller.
When to call a technician
If the reminder appears much earlier than due.

Codes from a single source

We found the following in only one source, with no second source confirming it, so it is kept here apart from the confirmed explanations above. Treat it as a first hint and check it against your appliance's manual.

CAN ECU Data Fail No data from the engine computer Needs a technician

What it means
The panel is set up for an electronic engine but isn't receiving data from it.
What you can do
Make sure the communication cable between the panel and the engine is connected, then switch off the generator, press Stop/Reset to clear the alarm, and restart.
When to call a technician
If the alarm stays.

CAN ECU Shutdown Shutdown from the engine computer Needs a technician

What it means
The engine control module sent a shutdown alarm.
What you can do
Note any number or message that appears with it, and don't keep restarting.
When to call a technician
Straight away. It needs an engine diagnostic tool.

Loss of Mag Pickup Signal No signal from the speed sensor Needs a technician

What it means
The magnetic speed sensor isn't sending a signal.
What you can do
Check the sensor's wire on the flywheel housing, then switch off the generator, press Stop/Reset to clear the alarm, and restart.
When to call a technician
If the alarm stays. The sensor may need adjusting or replacing.

Over Frequency Frequency high Needs a technician

What it means
The generator's frequency is above the set limit.
What you can do
Disconnect the loads and don't restart before it is checked.
When to call a technician
Straight away. The technician checks the governor and the speed setting.

Under Frequency Frequency low Try it yourself first

What it means
The generator's frequency is below the limit, usually because of an overload or a fuel shortage.
What you can do
Reduce the loads, check the fuel and the filter, then switch off the generator, press Stop/Reset to clear the alarm, and restart.
When to call a technician
If it keeps happening with light loads.

Digital Input Alarm from an auxiliary input Try it yourself first

What it means
An auxiliary input set up by the technician (such as a water level or the room door) gave a signal.
What you can do
Ask whoever installed the generator what this input monitors, fix the cause, then switch off the generator, press Stop/Reset to clear the alarm, and restart.
When to call a technician
If you don't know what the input monitors.