A3tali

Home ‹ Industrial drives ‹ INVT

INVT drive error codes

32 codes, each with what it means, what you can safely try yourself, and when to call a technician. Codes for the Goodrive series, which are abbreviations such as OC1 and OV2.

3 of the 32 entries on this page come from a single unconfirmed source, so they are listed separately at the end of the page.

A code's meaning can differ between models of the same brand. Check what you find here against your appliance's manual before any repair.

Quick table

CodeMeaningWho handles it
OUt1Phase U IGBT errorNeeds a technician
OUt2Phase V IGBT errorNeeds a technician
OUt3Phase W IGBT errorNeeds a technician
OC1Overcurrent during accelerationNeeds a technician
OC2Overcurrent during decelerationNeeds a technician
OC3Overcurrent at constant speedNeeds a technician
OV1Overvoltage during accelerationNeeds a technician
OV2Overvoltage during decelerationNeeds a technician
OV3Overvoltage at constant speedNeeds a technician
UVDC bus undervoltageNeeds a technician
OL1Motor overloadNeeds a technician
OL2Drive overloadNeeds a technician
OL3Electrical overloadNeeds a technician
SPIInput phase lossNeeds a technician
SPOOutput phase lossNeeds a technician
OH1Control board overheatingNeeds a technician
OH2IGBT overheatingNeeds a technician
EFExternal circuit faultNeeds a technician
CECommunication errorNeeds a technician
ItECurrent sensing circuit faultNeeds a technician
tEAuto-tuning errorNeeds a technician
EEPEEPROM memory errorNeeds a technician
PIDEPID feedback lossNeeds a technician
bCEBraking errorNeeds a technician
ETH1Short to earth 1Needs a technician
ETH2Short to earth 2Needs a technician
dEuSpeed deviationNeeds a technician
SToParameter calibration errorNeeds a technician
ENDRunning time reached the factory settingNeeds a technician
PCEKeypad communication errorNeeds a technician
DNEParameter download errorNeeds a technician
LLUnderloadNeeds a technician

Every code explained

Drive capacitors hold a lethal voltage for minutes after the supply is disconnected. Wait for the charge light to go out and measure the voltage before touching any terminal.

OUt1 Phase U IGBT error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.
Note
GD200A model. The official manual for the GD100-PV gives the same meaning for the corresponding fault

OUt2 Phase V IGBT error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OUt3 Phase W IGBT error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OC1 Overcurrent during acceleration Needs a technician

What it means
The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
What you can do
Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OC2 Overcurrent during deceleration Needs a technician

What it means
The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
What you can do
Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OC3 Overcurrent at constant speed Needs a technician

What it means
The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
What you can do
Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OV1 Overvoltage during acceleration Needs a technician

What it means
The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OV2 Overvoltage during deceleration Needs a technician

What it means
The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OV3 Overvoltage at constant speed Needs a technician

What it means
The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

UV DC bus undervoltage Needs a technician

What it means
The supply reaching the drive is deficient: low voltage, a missing phase, or a momentary dip.
What you can do
Make sure the breaker and fuses ahead of the drive are sound and all three phases are present.
When to call a technician
If the supply is sound and the code stays. The charging circuit and capacitors inside the drive are checked.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OL1 Motor overload Needs a technician

What it means
The motor or drive is running above its rated current for longer than allowed.
What you can do
Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
When to call a technician
If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OL2 Drive overload Needs a technician

What it means
The motor or drive is running above its rated current for longer than allowed.
What you can do
Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
When to call a technician
If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OL3 Electrical overload Needs a technician

What it means
The motor or drive is running above its rated current for longer than allowed.
What you can do
Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
When to call a technician
If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

SPI Input phase loss Needs a technician

What it means
The supply reaching the drive is deficient: low voltage, a missing phase, or a momentary dip.
What you can do
Make sure the breaker and fuses ahead of the drive are sound and all three phases are present.
When to call a technician
If the supply is sound and the code stays. The charging circuit and capacitors inside the drive are checked.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

SPO Output phase loss Needs a technician

What it means
One of the three phases between the drive and the motor is broken or unbalanced.
What you can do
Disconnect the supply and don't run the motor on two phases.
When to call a technician
In every case. The motor cable terminals are checked at the drive and at the motor, and any contactor between them.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

OH2 IGBT overheating Needs a technician

What it means
The drive or motor temperature is outside the allowed limit.
What you can do
Clean the dust off the panel filters and the drive's heat sink, and make sure its fan turns and the room temperature is acceptable.
When to call a technician
If the code stays with good ventilation. The fan or the temperature sensor is replaced.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

EF External circuit fault Needs a technician

What it means
An external input is preventing operation: an open safety circuit, an emergency stop, or a fault signal from another device.
What you can do
Make sure the emergency stop is released and the guard doors are closed.
When to call a technician
If the safety circuit is sound and the code stays.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

CE Communication error Needs a technician

What it means
The drive lost contact with its keypad or with the controller that sends it commands.
What you can do
Make sure the communication cable and the keypad are seated properly.
When to call a technician
If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

ItE Current sensing circuit fault Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

tE Auto-tuning error Needs a technician

What it means
The drive couldn't measure the motor's characteristics during auto-tuning.
What you can do
Make sure the motor is connected and unloaded, and its nameplate data is entered correctly, then repeat the tuning.
When to call a technician
If it fails again.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

EEP EEPROM memory error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

PIDE PID feedback loss Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

bCE Braking error Needs a technician

What it means
A fault in the braking circuit or its resistor.
What you can do
Disconnect the supply and don't keep restarting.
When to call a technician
In every case. The braking resistor and its transistor are checked.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

ETH1 Short to earth 1 Needs a technician

What it means
Current is leaking from one of the output phases to earth, usually from the motor cable or windings.
What you can do
Disconnect the supply and don't keep restarting.
When to call a technician
In every case. The insulation of the motor cable and windings is measured with a megger after disconnecting them from the drive.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

ETH2 Short to earth 2 Needs a technician

What it means
Current is leaking from one of the output phases to earth, usually from the motor cable or windings.
What you can do
Disconnect the supply and don't keep restarting.
When to call a technician
In every case. The insulation of the motor cable and windings is measured with a megger after disconnecting them from the drive.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

dEu Speed deviation Needs a technician

What it means
The motor's actual speed doesn't match what the drive is asking for, or the rotation sensor signal is lost.
What you can do
Make sure the load isn't jammed, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The encoder, its cable and the control settings are checked.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

STo Parameter calibration error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

END Running time reached the factory setting Needs a technician

What it means
The drive reached the number of running hours set for an alert. A maintenance reminder, not a fault.
What you can do
Carry out the scheduled maintenance, then reset the timer as the manual explains.
When to call a technician
If the timer won't reset.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

LL Underload Needs a technician

What it means
The load on the motor is much lighter than expected: a broken belt, a disconnected coupling, or a pump running dry.
What you can do
Stop the motor and check its connection to the machine and that water is reaching the pump.
When to call a technician
If the load is connected and the code stays. The underload limit value in the settings is reviewed.
Note
The official manual for the GD100-PV gives the same meaning for the corresponding fault

Codes from a single source

We found the following in only one source, with no second source confirming it, so it is kept here apart from the confirmed explanations above. Treat it as a first hint and check it against your appliance's manual.

OH1 Control board overheating Needs a technician

What it means
The drive or motor temperature is outside the allowed limit.
What you can do
Clean the dust off the panel filters and the drive's heat sink, and make sure its fan turns and the room temperature is acceptable.
When to call a technician
If the code stays with good ventilation. The fan or the temperature sensor is replaced.

PCE Keypad communication error Needs a technician

What it means
The drive lost contact with its keypad or with the controller that sends it commands.
What you can do
Make sure the communication cable and the keypad are seated properly.
When to call a technician
If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.

DNE Parameter download error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

Sources