Quick table
| Code | Meaning | Who handles it |
|---|
OUt1 | Phase U IGBT error | Needs a technician |
OUt2 | Phase V IGBT error | Needs a technician |
OUt3 | Phase W IGBT error | Needs a technician |
OC1 | Overcurrent during acceleration | Needs a technician |
OC2 | Overcurrent during deceleration | Needs a technician |
OC3 | Overcurrent at constant speed | Needs a technician |
OV1 | Overvoltage during acceleration | Needs a technician |
OV2 | Overvoltage during deceleration | Needs a technician |
OV3 | Overvoltage at constant speed | Needs a technician |
UV | DC bus undervoltage | Needs a technician |
OL1 | Motor overload | Needs a technician |
OL2 | Drive overload | Needs a technician |
OL3 | Electrical overload | Needs a technician |
SPI | Input phase loss | Needs a technician |
SPO | Output phase loss | Needs a technician |
OH1 | Control board overheating | Needs a technician |
OH2 | IGBT overheating | Needs a technician |
EF | External circuit fault | Needs a technician |
CE | Communication error | Needs a technician |
ItE | Current sensing circuit fault | Needs a technician |
tE | Auto-tuning error | Needs a technician |
EEP | EEPROM memory error | Needs a technician |
PIDE | PID feedback loss | Needs a technician |
bCE | Braking error | Needs a technician |
ETH1 | Short to earth 1 | Needs a technician |
ETH2 | Short to earth 2 | Needs a technician |
dEu | Speed deviation | Needs a technician |
STo | Parameter calibration error | Needs a technician |
END | Running time reached the factory setting | Needs a technician |
PCE | Keypad communication error | Needs a technician |
DNE | Parameter download error | Needs a technician |
LL | Underload | Needs a technician |
Every code explained
Drive capacitors hold a lethal voltage for minutes after the supply is disconnected. Wait for the charge light to go out and measure the voltage before touching any terminal.
OUt1 Phase U IGBT error Needs a technician
- What it means
- An internal drive fault: memory, processor or one of the circuits.
- What you can do
- Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. It may need a factory reset or a board replacement.
- Note
- GD200A model. The official manual for the GD100-PV gives the same meaning for the corresponding fault
OUt2 Phase V IGBT error Needs a technician
- What it means
- An internal drive fault: memory, processor or one of the circuits.
- What you can do
- Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. It may need a factory reset or a board replacement.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OUt3 Phase W IGBT error Needs a technician
- What it means
- An internal drive fault: memory, processor or one of the circuits.
- What you can do
- Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. It may need a factory reset or a board replacement.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OC1 Overcurrent during acceleration Needs a technician
- What it means
- The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
- What you can do
- Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OC2 Overcurrent during deceleration Needs a technician
- What it means
- The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
- What you can do
- Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OC3 Overcurrent at constant speed Needs a technician
- What it means
- The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
- What you can do
- Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OV1 Overvoltage during acceleration Needs a technician
- What it means
- The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
- What you can do
- Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OV2 Overvoltage during deceleration Needs a technician
- What it means
- The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
- What you can do
- Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OV3 Overvoltage at constant speed Needs a technician
- What it means
- The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
- What you can do
- Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
UV DC bus undervoltage Needs a technician
- What it means
- The supply reaching the drive is deficient: low voltage, a missing phase, or a momentary dip.
- What you can do
- Make sure the breaker and fuses ahead of the drive are sound and all three phases are present.
- When to call a technician
- If the supply is sound and the code stays. The charging circuit and capacitors inside the drive are checked.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OL1 Motor overload Needs a technician
- What it means
- The motor or drive is running above its rated current for longer than allowed.
- What you can do
- Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
- When to call a technician
- If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OL2 Drive overload Needs a technician
- What it means
- The motor or drive is running above its rated current for longer than allowed.
- What you can do
- Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
- When to call a technician
- If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OL3 Electrical overload Needs a technician
- What it means
- The motor or drive is running above its rated current for longer than allowed.
- What you can do
- Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
- When to call a technician
- If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
SPI Input phase loss Needs a technician
- What it means
- The supply reaching the drive is deficient: low voltage, a missing phase, or a momentary dip.
- What you can do
- Make sure the breaker and fuses ahead of the drive are sound and all three phases are present.
- When to call a technician
- If the supply is sound and the code stays. The charging circuit and capacitors inside the drive are checked.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
SPO Output phase loss Needs a technician
- What it means
- One of the three phases between the drive and the motor is broken or unbalanced.
- What you can do
- Disconnect the supply and don't run the motor on two phases.
- When to call a technician
- In every case. The motor cable terminals are checked at the drive and at the motor, and any contactor between them.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
OH2 IGBT overheating Needs a technician
- What it means
- The drive or motor temperature is outside the allowed limit.
- What you can do
- Clean the dust off the panel filters and the drive's heat sink, and make sure its fan turns and the room temperature is acceptable.
- When to call a technician
- If the code stays with good ventilation. The fan or the temperature sensor is replaced.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
EF External circuit fault Needs a technician
- What it means
- An external input is preventing operation: an open safety circuit, an emergency stop, or a fault signal from another device.
- What you can do
- Make sure the emergency stop is released and the guard doors are closed.
- When to call a technician
- If the safety circuit is sound and the code stays.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
CE Communication error Needs a technician
- What it means
- The drive lost contact with its keypad or with the controller that sends it commands.
- What you can do
- Make sure the communication cable and the keypad are seated properly.
- When to call a technician
- If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
ItE Current sensing circuit fault Needs a technician
- What it means
- An internal drive fault: memory, processor or one of the circuits.
- What you can do
- Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. It may need a factory reset or a board replacement.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
tE Auto-tuning error Needs a technician
- What it means
- The drive couldn't measure the motor's characteristics during auto-tuning.
- What you can do
- Make sure the motor is connected and unloaded, and its nameplate data is entered correctly, then repeat the tuning.
- When to call a technician
- If it fails again.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
EEP EEPROM memory error Needs a technician
- What it means
- An internal drive fault: memory, processor or one of the circuits.
- What you can do
- Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. It may need a factory reset or a board replacement.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
PIDE PID feedback loss Needs a technician
- What it means
- The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
- What you can do
- Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
- When to call a technician
- If the sensor and the pump are fine and the code stays.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
bCE Braking error Needs a technician
- What it means
- A fault in the braking circuit or its resistor.
- What you can do
- Disconnect the supply and don't keep restarting.
- When to call a technician
- In every case. The braking resistor and its transistor are checked.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
ETH1 Short to earth 1 Needs a technician
- What it means
- Current is leaking from one of the output phases to earth, usually from the motor cable or windings.
- What you can do
- Disconnect the supply and don't keep restarting.
- When to call a technician
- In every case. The insulation of the motor cable and windings is measured with a megger after disconnecting them from the drive.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
ETH2 Short to earth 2 Needs a technician
- What it means
- Current is leaking from one of the output phases to earth, usually from the motor cable or windings.
- What you can do
- Disconnect the supply and don't keep restarting.
- When to call a technician
- In every case. The insulation of the motor cable and windings is measured with a megger after disconnecting them from the drive.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
dEu Speed deviation Needs a technician
- What it means
- The motor's actual speed doesn't match what the drive is asking for, or the rotation sensor signal is lost.
- What you can do
- Make sure the load isn't jammed, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. The encoder, its cable and the control settings are checked.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
STo Parameter calibration error Needs a technician
- What it means
- An internal drive fault: memory, processor or one of the circuits.
- What you can do
- Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. It may need a factory reset or a board replacement.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
END Running time reached the factory setting Needs a technician
- What it means
- The drive reached the number of running hours set for an alert. A maintenance reminder, not a fault.
- What you can do
- Carry out the scheduled maintenance, then reset the timer as the manual explains.
- When to call a technician
- If the timer won't reset.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
LL Underload Needs a technician
- What it means
- The load on the motor is much lighter than expected: a broken belt, a disconnected coupling, or a pump running dry.
- What you can do
- Stop the motor and check its connection to the machine and that water is reaching the pump.
- When to call a technician
- If the load is connected and the code stays. The underload limit value in the settings is reviewed.
- Note
- The official manual for the GD100-PV gives the same meaning for the corresponding fault
Codes from a single source
We found the following in only one source, with no second source confirming it, so it is kept here apart from the confirmed explanations above. Treat it as a first hint and check it against your appliance's manual.
OH1 Control board overheating Needs a technician
- What it means
- The drive or motor temperature is outside the allowed limit.
- What you can do
- Clean the dust off the panel filters and the drive's heat sink, and make sure its fan turns and the room temperature is acceptable.
- When to call a technician
- If the code stays with good ventilation. The fan or the temperature sensor is replaced.
PCE Keypad communication error Needs a technician
- What it means
- The drive lost contact with its keypad or with the controller that sends it commands.
- What you can do
- Make sure the communication cable and the keypad are seated properly.
- When to call a technician
- If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.
DNE Parameter download error Needs a technician
- What it means
- An internal drive fault: memory, processor or one of the circuits.
- What you can do
- Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
- When to call a technician
- If the code comes back. It may need a factory reset or a board replacement.