Fuji Electric drive error codes

45 codes, each with what it means, what you can safely try yourself, and when to call a technician. Codes for the FRENIC-HVAC series.

A code's meaning can differ between models of the same brand. Check what you find here against your appliance's manual before any repair.

Quick table

CodeMeaningWho handles it
OC1Instantaneous overcurrent during accelerationNeeds a technician
OC2Instantaneous overcurrent during decelerationNeeds a technician
OC3Instantaneous overcurrent at constant speedNeeds a technician
EFEarth faultNeeds a technician
OV1Overvoltage during accelerationNeeds a technician
OV2Overvoltage during decelerationNeeds a technician
OV3Overvoltage at constant speedNeeds a technician
LVUndervoltageNeeds a technician
LiNInput phase lossNeeds a technician
OPLOutput phase lossNeeds a technician
OH1Heat sink overheatingNeeds a technician
OH2External alarmNeeds a technician
OH3Overheating inside the driveNeeds a technician
OH4PTC thermistor motor protectionNeeds a technician
FUSFuse blownNeeds a technician
PbFCharging circuit faultNeeds a technician
OL1Motor 1 overloadNeeds a technician
OLUDrive overloadNeeds a technician
Er1Memory errorNeeds a technician
Er2Keypad communication errorNeeds a technician
Er3CPU errorNeeds a technician
Er4Option communication errorNeeds a technician
Er5Option errorNeeds a technician
Er6Operation protectionNeeds a technician
Er7Auto-tuning errorNeeds a technician
Er8RS-485 communication error, port 1Needs a technician
ErPRS-485 communication error, port 2Needs a technician
ErFData save error on undervoltageNeeds a technician
ErHHardware errorNeeds a technician
CoFCurrent input disconnection detectedNeeds a technician
ECLCustomisable logic errorNeeds a technician
ECFEnable circuit errorNeeds a technician
PV1PID 1 feedback errorNeeds a technician
PV2PID 2 feedback errorNeeds a technician
PVAExternal PID 1 feedback errorNeeds a technician
PVBExternal PID 2 feedback errorNeeds a technician
PVCExternal PID 3 feedback errorNeeds a technician
PdrDry-run protectionNeeds a technician
roCStarts per hour exceededNeeds a technician
PoLEnd-of-curve pump protectionNeeds a technician
rLoAnti-jamNeeds a technician
FoLFilter cloggedNeeds a technician
LoKDrive locked by passwordNeeds a technician
LobBattery lowNeeds a technician
dtLDate information lostNeeds a technician

Every code explained

Drive capacitors hold a lethal voltage for minutes after the supply is disconnected. Wait for the charge light to go out and measure the voltage before touching any terminal.

OC1 Instantaneous overcurrent during acceleration Needs a technician

What it means
The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
What you can do
Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.
Note
FRENIC-HVAC series

OC2 Instantaneous overcurrent during deceleration Needs a technician

What it means
The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
What you can do
Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.

OC3 Instantaneous overcurrent at constant speed Needs a technician

What it means
The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
What you can do
Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.

EF Earth fault Needs a technician

What it means
Current is leaking from one of the output phases to earth, usually from the motor cable or windings.
What you can do
Disconnect the supply and don't keep restarting.
When to call a technician
In every case. The insulation of the motor cable and windings is measured with a megger after disconnecting them from the drive.

OV1 Overvoltage during acceleration Needs a technician

What it means
The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.

OV2 Overvoltage during deceleration Needs a technician

What it means
The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.

OV3 Overvoltage at constant speed Needs a technician

What it means
The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.

LV Undervoltage Needs a technician

What it means
The supply reaching the drive is deficient: low voltage, a missing phase, or a momentary dip.
What you can do
Make sure the breaker and fuses ahead of the drive are sound and all three phases are present.
When to call a technician
If the supply is sound and the code stays. The charging circuit and capacitors inside the drive are checked.

LiN Input phase loss Needs a technician

What it means
The supply reaching the drive is deficient: low voltage, a missing phase, or a momentary dip.
What you can do
Make sure the breaker and fuses ahead of the drive are sound and all three phases are present.
When to call a technician
If the supply is sound and the code stays. The charging circuit and capacitors inside the drive are checked.

OPL Output phase loss Needs a technician

What it means
One of the three phases between the drive and the motor is broken or unbalanced.
What you can do
Disconnect the supply and don't run the motor on two phases.
When to call a technician
In every case. The motor cable terminals are checked at the drive and at the motor, and any contactor between them.

OH1 Heat sink overheating Needs a technician

What it means
The drive or motor temperature is outside the allowed limit.
What you can do
Clean the dust off the panel filters and the drive's heat sink, and make sure its fan turns and the room temperature is acceptable.
When to call a technician
If the code stays with good ventilation. The fan or the temperature sensor is replaced.

OH2 External alarm Needs a technician

What it means
An external input is preventing operation: an open safety circuit, an emergency stop, or a fault signal from another device.
What you can do
Make sure the emergency stop is released and the guard doors are closed.
When to call a technician
If the safety circuit is sound and the code stays.

OH3 Overheating inside the drive Needs a technician

What it means
The drive or motor temperature is outside the allowed limit.
What you can do
Clean the dust off the panel filters and the drive's heat sink, and make sure its fan turns and the room temperature is acceptable.
When to call a technician
If the code stays with good ventilation. The fan or the temperature sensor is replaced.

OH4 PTC thermistor motor protection Needs a technician

What it means
The drive or motor temperature is outside the allowed limit.
What you can do
Clean the dust off the panel filters and the drive's heat sink, and make sure its fan turns and the room temperature is acceptable.
When to call a technician
If the code stays with good ventilation. The fan or the temperature sensor is replaced.

FUS Fuse blown Needs a technician

What it means
The supply reaching the drive is deficient: low voltage, a missing phase, or a momentary dip.
What you can do
Make sure the breaker and fuses ahead of the drive are sound and all three phases are present.
When to call a technician
If the supply is sound and the code stays. The charging circuit and capacitors inside the drive are checked.

PbF Charging circuit fault Needs a technician

What it means
The supply reaching the drive is deficient: low voltage, a missing phase, or a momentary dip.
What you can do
Make sure the breaker and fuses ahead of the drive are sound and all three phases are present.
When to call a technician
If the supply is sound and the code stays. The charging circuit and capacitors inside the drive are checked.

OL1 Motor 1 overload Needs a technician

What it means
The motor or drive is running above its rated current for longer than allowed.
What you can do
Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
When to call a technician
If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.

OLU Drive overload Needs a technician

What it means
The motor or drive is running above its rated current for longer than allowed.
What you can do
Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
When to call a technician
If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.

Er1 Memory error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

Er2 Keypad communication error Needs a technician

What it means
The drive lost contact with its keypad or with the controller that sends it commands.
What you can do
Make sure the communication cable and the keypad are seated properly.
When to call a technician
If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.

Er3 CPU error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

Er4 Option communication error Needs a technician

What it means
The drive lost contact with its keypad or with the controller that sends it commands.
What you can do
Make sure the communication cable and the keypad are seated properly.
When to call a technician
If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.

Er5 Option error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

Er6 Operation protection Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

Er7 Auto-tuning error Needs a technician

What it means
The drive couldn't measure the motor's characteristics during auto-tuning.
What you can do
Make sure the motor is connected and unloaded, and its nameplate data is entered correctly, then repeat the tuning.
When to call a technician
If it fails again.

Er8 RS-485 communication error, port 1 Needs a technician

What it means
The drive lost contact with its keypad or with the controller that sends it commands.
What you can do
Make sure the communication cable and the keypad are seated properly.
When to call a technician
If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.

ErP RS-485 communication error, port 2 Needs a technician

What it means
The drive lost contact with its keypad or with the controller that sends it commands.
What you can do
Make sure the communication cable and the keypad are seated properly.
When to call a technician
If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.

ErF Data save error on undervoltage Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

ErH Hardware error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

CoF Current input disconnection detected Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

ECL Customisable logic error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

ECF Enable circuit error Needs a technician

What it means
An external input is preventing operation: an open safety circuit, an emergency stop, or a fault signal from another device.
What you can do
Make sure the emergency stop is released and the guard doors are closed.
When to call a technician
If the safety circuit is sound and the code stays.

PV1 PID 1 feedback error Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

PV2 PID 2 feedback error Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

PVA External PID 1 feedback error Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

PVB External PID 2 feedback error Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

PVC External PID 3 feedback error Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

Pdr Dry-run protection Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

roC Starts per hour exceeded Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

PoL End-of-curve pump protection Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

rLo Anti-jam Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

FoL Filter clogged Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

LoK Drive locked by password Needs a technician

What it means
The keypad or the settings are deliberately locked.
What you can do
Unlock it as described in the drive's manual or with the password.
When to call a technician
If the password is lost.

Lob Battery low Needs a technician

What it means
The internal clock battery is weak, so the date and time are lost or about to be.
What you can do
The drive runs, but schedules and the fault log are affected.
When to call a technician
To replace the battery and reset the time.

dtL Date information lost Needs a technician

What it means
The internal clock battery is weak, so the date and time are lost or about to be.
What you can do
The drive runs, but schedules and the fault log are affected.
When to call a technician
To replace the battery and reset the time.