A3tali

Home ‹ Pump inverters ‹ INVT

INVT pump inverter error codes

44 codes, each with what it means, what you can safely try yourself, and when to call a technician. Codes for the Goodrive100-PV series from the manufacturer's manual.

A code's meaning can differ between models of the same brand. Check what you find here against your appliance's manual before any repair.

Quick table

CodeMeaningWho handles it
1Phase U protection in the inverter moduleNeeds a technician
2Phase V protection in the inverter moduleNeeds a technician
3Phase W protection in the inverter moduleNeeds a technician
4Overcurrent during accelerationNeeds a technician
5Overcurrent during decelerationNeeds a technician
6Overcurrent at constant speedNeeds a technician
7Overvoltage during accelerationNeeds a technician
8Overvoltage during decelerationNeeds a technician
9Overvoltage at constant speedNeeds a technician
10Internal DC bus undervoltageNeeds a technician
11Motor overloadNeeds a technician
12Drive overloadNeeds a technician
13Input phase lossNeeds a technician
14Output phase lossNeeds a technician
15Boost module overheatingNeeds a technician
16Inverter module overheatingNeeds a technician
17External faultNeeds a technician
18RS485 communication faultNeeds a technician
19Current measurement faultNeeds a technician
20Motor auto-tuning failedNeeds a technician
21EEPROM memory errorNeeds a technician
22PID feedback disconnectedNeeds a technician
23Braking unit faultNeeds a technician
24Running time reached the set limitNot a fault
25Electronic overloadNeeds a technician
32Short to earth 1Needs a technician
33Short to earth 2Needs a technician
34Speed deviationNeeds a technician
35Setting errorNeeds a technician
36UnderloadTry it yourself first
37Water level probe damagedNeeds a technician
38Panels connected with reversed polarityNeeds a technician
39Overcurrent from the panelsNeeds a technician
40Overvoltage from the panelsNeeds a technician
41Panel voltage lowTry it yourself first
42422 communication fault with the boost moduleNeeds a technician
43Overvoltage on the boost module busNeeds a technician
44Sunlight weakNot a fault
45Output imbalanceNeeds a technician
A-LSLow light alarmNot a fault
A-LLUnderload alarmTry it yourself first
A-tFTank full alarmNot a fault
A-tLTank or well empty alarmTry it yourself first
A-SPIMains power not connectedTry it yourself first

Every code explained

Panel voltage is lethal as long as the sun is up, and the inverter's capacitors hold their charge after switching off.

1 Phase U protection in the inverter module Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.
Note
The numbers are the fault numbers in the GD100-PV manual's table

2 Phase V protection in the inverter module Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

3 Phase W protection in the inverter module Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

4 Overcurrent during acceleration Needs a technician

What it means
The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
What you can do
Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.

5 Overcurrent during deceleration Needs a technician

What it means
The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
What you can do
Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.

6 Overcurrent at constant speed Needs a technician

What it means
The current suddenly rose above the drive's limit: a heavy load, acceleration that is too fast, or a short in the motor or its cable.
What you can do
Make sure the mechanical load isn't jammed and turns by hand, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The acceleration or deceleration time is increased, and the motor and its cable are insulation-tested.

7 Overvoltage during acceleration Needs a technician

What it means
The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.

8 Overvoltage during deceleration Needs a technician

What it means
The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.

9 Overvoltage at constant speed Needs a technician

What it means
The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.

10 Internal DC bus undervoltage Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

11 Motor overload Needs a technician

What it means
The motor or drive is running above its rated current for longer than allowed.
What you can do
Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
When to call a technician
If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.

12 Drive overload Needs a technician

What it means
The motor or drive is running above its rated current for longer than allowed.
What you can do
Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
When to call a technician
If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.

13 Input phase loss Needs a technician

What it means
The supply reaching the drive is deficient: low voltage, a missing phase, or a momentary dip.
What you can do
Make sure the breaker and fuses ahead of the drive are sound and all three phases are present.
When to call a technician
If the supply is sound and the code stays. The charging circuit and capacitors inside the drive are checked.

14 Output phase loss Needs a technician

What it means
One of the three phases between the drive and the motor is broken or unbalanced.
What you can do
Disconnect the supply and don't run the motor on two phases.
When to call a technician
In every case. The motor cable terminals are checked at the drive and at the motor, and any contactor between them.

15 Boost module overheating Needs a technician

What it means
The drive or motor temperature is outside the allowed limit.
What you can do
Clean the dust off the panel filters and the drive's heat sink, and make sure its fan turns and the room temperature is acceptable.
When to call a technician
If the code stays with good ventilation. The fan or the temperature sensor is replaced.

16 Inverter module overheating Needs a technician

What it means
The drive or motor temperature is outside the allowed limit.
What you can do
Clean the dust off the panel filters and the drive's heat sink, and make sure its fan turns and the room temperature is acceptable.
When to call a technician
If the code stays with good ventilation. The fan or the temperature sensor is replaced.

17 External fault Needs a technician

What it means
An external input is preventing operation: an open safety circuit, an emergency stop, or a fault signal from another device.
What you can do
Make sure the emergency stop is released and the guard doors are closed.
When to call a technician
If the safety circuit is sound and the code stays.

18 RS485 communication fault Needs a technician

What it means
The drive lost contact with its keypad or with the controller that sends it commands.
What you can do
Make sure the communication cable and the keypad are seated properly.
When to call a technician
If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.

19 Current measurement fault Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

20 Motor auto-tuning failed Needs a technician

What it means
The drive couldn't measure the motor's characteristics during auto-tuning.
What you can do
Make sure the motor is connected and unloaded, and its nameplate data is entered correctly, then repeat the tuning.
When to call a technician
If it fails again.

21 EEPROM memory error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

22 PID feedback disconnected Needs a technician

What it means
The signal from the external sensor the drive uses to control the process is lost or out of range, or a pump-specific protection was triggered.
What you can do
Check the sensor and its wire, and make sure water is reaching the pump and nothing is blocking it.
When to call a technician
If the sensor and the pump are fine and the code stays.

23 Braking unit fault Needs a technician

What it means
A fault in the braking circuit or its resistor.
What you can do
Disconnect the supply and don't keep restarting.
When to call a technician
In every case. The braking resistor and its transistor are checked.

24 Running time reached the set limit Not a fault

What it means
An operating state, not a fault.
What you can do
Nothing needs fixing.
When to call a technician
If the status persists and prevents pumping for no clear reason.

25 Electronic overload Needs a technician

What it means
The motor or drive is running above its rated current for longer than allowed.
What you can do
Reduce the load, and make sure the machine isn't jammed and the motor's ventilation isn't blocked.
When to call a technician
If it keeps happening with a normal load. The motor current value entered in the settings and the drive's size are reviewed.

32 Short to earth 1 Needs a technician

What it means
Current is leaking from one of the output phases to earth, usually from the motor cable or windings.
What you can do
Disconnect the supply and don't keep restarting.
When to call a technician
In every case. The insulation of the motor cable and windings is measured with a megger after disconnecting them from the drive.

33 Short to earth 2 Needs a technician

What it means
Current is leaking from one of the output phases to earth, usually from the motor cable or windings.
What you can do
Disconnect the supply and don't keep restarting.
When to call a technician
In every case. The insulation of the motor cable and windings is measured with a megger after disconnecting them from the drive.

34 Speed deviation Needs a technician

What it means
The motor's actual speed doesn't match what the drive is asking for, or the rotation sensor signal is lost.
What you can do
Make sure the load isn't jammed, then stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. The encoder, its cable and the control settings are checked.

35 Setting error Needs a technician

What it means
An internal drive fault: memory, processor or one of the circuits.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If the code comes back. It may need a factory reset or a board replacement.

36 Underload Try it yourself first

What it means
The load on the motor is much lighter than expected: a broken belt, a disconnected coupling, or a pump running dry.
What the source says
The pump is most likely running without water
What you can do
Stop the motor and check its connection to the machine and that water is reaching the pump.
When to call a technician
If the load is connected and the code stays. The underload limit value in the settings is reviewed.

37 Water level probe damaged Needs a technician

What it means
The water level probe reports that the tank is full or the well is empty, so the inverter stopped the pump.
What you can do
Check the actual water level, and that the probe is in place and its wire is sound.
When to call a technician
If the level is normal and the alarm stays.

38 Panels connected with reversed polarity Needs a technician

What it means
A problem with the panel connection: reversed polarity, or voltage or current outside the inverter's limit.
What you can do
Don't disconnect the panel connections while the sun is shining.
When to call a technician
In every case. The number of panels and their connection are reviewed.

39 Overcurrent from the panels Needs a technician

What it means
A problem with the panel connection: reversed polarity, or voltage or current outside the inverter's limit.
What you can do
Don't disconnect the panel connections while the sun is shining.
When to call a technician
In every case. The number of panels and their connection are reviewed.

40 Overvoltage from the panels Needs a technician

What it means
A problem with the panel connection: reversed polarity, or voltage or current outside the inverter's limit.
What you can do
Don't disconnect the panel connections while the sun is shining.
When to call a technician
In every case. The number of panels and their connection are reviewed.

41 Panel voltage low Try it yourself first

What it means
A problem with the panel connection: reversed polarity, or voltage or current outside the inverter's limit.
What you can do
Don't disconnect the panel connections while the sun is shining.
When to call a technician
In every case. The number of panels and their connection are reviewed.

42 422 communication fault with the boost module Needs a technician

What it means
The drive lost contact with its keypad or with the controller that sends it commands.
What you can do
Make sure the communication cable and the keypad are seated properly.
When to call a technician
If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.

43 Overvoltage on the boost module bus Needs a technician

What it means
The DC bus voltage inside the drive rose above the limit. It usually happens when stopping a high-inertia load quickly, or with a high supply voltage.
What you can do
Stop the motor, disconnect the drive's supply and wait until its display and charge light go out, then restart.
When to call a technician
If it keeps happening. The deceleration time is increased or a braking resistor fitted, and the supply voltage is measured.

44 Sunlight weak Not a fault

What it means
An operating state, not a fault.
What you can do
Nothing needs fixing.
When to call a technician
If the status persists and prevents pumping for no clear reason.

45 Output imbalance Needs a technician

What it means
One of the three phases between the drive and the motor is broken or unbalanced.
What you can do
Disconnect the supply and don't run the motor on two phases.
When to call a technician
In every case. The motor cable terminals are checked at the drive and at the motor, and any contactor between them.

A-LS Low light alarm Not a fault

What it means
An operating state, not a fault.
What the source says
Solar irradiance insufficient
What you can do
Nothing needs fixing.
When to call a technician
If the status persists and prevents pumping for no clear reason.

A-LL Underload alarm Try it yourself first

What it means
The load on the motor is much lighter than expected: a broken belt, a disconnected coupling, or a pump running dry.
What you can do
Stop the motor and check its connection to the machine and that water is reaching the pump.
When to call a technician
If the load is connected and the code stays. The underload limit value in the settings is reviewed.

A-tF Tank full alarm Not a fault

What it means
An operating state, not a fault.
What you can do
Nothing needs fixing.
When to call a technician
If the status persists and prevents pumping for no clear reason.

A-tL Tank or well empty alarm Try it yourself first

What it means
The water level probe reports that the tank is full or the well is empty, so the inverter stopped the pump.
What you can do
Check the actual water level, and that the probe is in place and its wire is sound.
When to call a technician
If the level is normal and the alarm stays.

A-SPI Mains power not connected Try it yourself first

What it means
The drive lost contact with its keypad or with the controller that sends it commands.
What you can do
Make sure the communication cable and the keypad are seated properly.
When to call a technician
If the code stays. The communication settings, address and speed are reviewed, and the cable is checked for interference.