Home ‹ Air conditioners ‹ TCL

TCL air conditioner error codes

26 codes, each with what it means, what you can safely try yourself, and when to call a technician.

All the codes on this page come from a single unofficial source, and we have not yet found a second one confirming them. Treat them as a first hint and check them against your appliance's manual before any repair.

A code's meaning can differ between models of the same brand. Check what you find here against your appliance's manual before any repair.

Quick table

CodeMeaningWho handles it
E0Indoor–outdoor unit communication faultTry it yourself first
E1Room temperature sensor faultNeeds a technician
E2Indoor coil pipe sensor faultNeeds a technician
E3Outdoor coil pipe sensor faultNeeds a technician
E4Pressure or refrigerant level faultNeeds a technician
E5Model setting mismatch between the unitsNeeds a technician
E6Indoor fan motor fault or blades jammedNeeds a technician
E7Outdoor unit temperature sensor faultNeeds a technician
E8Discharge temperature sensor faultNeeds a technician
E9IPM power module faultNeeds a technician
EACurrent sensor fault or refrigerant leakNeeds a technician
ECCommunication fault inside the outdoor unit boardNeeds a technician
EEDamaged memory chip (EEPROM)Needs a technician
EFOutdoor DC fan motor faultNeeds a technician
EHOutdoor unit suction temperature sensor faultNeeds a technician
EPCompressor thermal switch faultNeeds a technician
EUVoltage sensor or its connection faultNeeds a technician
P0Power module protectionNeeds a technician
P1High or low voltage protectionNeeds a technician
P2Overcurrent protectionNeeds a technician
P4High discharge temperature protectionNeeds a technician
P5Overcooling protection in cooling modeNeeds a technician
P6Overheating protection in cooling modeTry it yourself first
P7Overheating protection in heating modeTry it yourself first
P8Protection against outdoor temperature above or below the limitNot a fault
P9Software protection of the drive circuitNeeds a technician

Every code explained

Everything under “What you can do” is done without opening any cover. Opening the air conditioner or measuring its wiring with the power on is a technician's job.

E0 Indoor–outdoor unit communication fault Try it yourself first

What it means
The indoor and outdoor units (or two boards inside the unit) exchange a signal over a wire, and that signal has been lost.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Make sure the outdoor unit's breaker is on. Note whether the code started after installation, relocation or a power cut.
When to call a technician
If the code comes back after restarting. Checking the cable and terminals is done with the power on, which is a technician's job.
Note
Another site gives a completely different list of TCL codes

E1 Room temperature sensor fault Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

E2 Indoor coil pipe sensor fault Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

E3 Outdoor coil pipe sensor fault Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

E4 Pressure or refrigerant level fault Needs a technician

What it means
There is less refrigerant in the system than needed, usually because of a leak.
What you can do
Clean the filter and confirm that cooling really is weak. There is nothing else to do on your side.
When to call a technician
In almost every case. Ask the technician to find and repair the leak before recharging; recharging alone is only a temporary fix.

E5 Model setting mismatch between the units Needs a technician

What it means
The air conditioner detected a fault and stopped because of it.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back after restarting.

E6 Indoor fan motor fault or blades jammed Needs a technician

What it means
The fan is not turning, or it turns but the unit does not receive its rotation signal.
What you can do
Turn the unit off and check whether anything is blocking the fan: built-up dirt, a leaf or a foreign object. Never put your hand in while the power is on.
When to call a technician
If the fan turns freely but does not run. The motor, its capacitor or the board needs testing.

E7 Outdoor unit temperature sensor fault Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

E8 Discharge temperature sensor fault Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

E9 IPM power module fault Needs a technician

What it means
A fault in the electronic control board or one of its parts.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Sometimes the fault is temporary after a power fluctuation.
When to call a technician
If the code comes back. The board is tested and repaired or replaced; ask for a diagnosis before agreeing to replace it, as it is one of the most expensive parts.

EA Current sensor fault or refrigerant leak Needs a technician

What it means
There is less refrigerant in the system than needed, usually because of a leak.
What you can do
Clean the filter and confirm that cooling really is weak. There is nothing else to do on your side.
When to call a technician
In almost every case. Ask the technician to find and repair the leak before recharging; recharging alone is only a temporary fix.

EC Communication fault inside the outdoor unit board Needs a technician

What it means
The indoor and outdoor units (or two boards inside the unit) exchange a signal over a wire, and that signal has been lost.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Make sure the outdoor unit's breaker is on. Note whether the code started after installation, relocation or a power cut.
When to call a technician
If the code comes back after restarting. Checking the cable and terminals is done with the power on, which is a technician's job.

EE Damaged memory chip (EEPROM) Needs a technician

What it means
A fault in the electronic control board or one of its parts.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Sometimes the fault is temporary after a power fluctuation.
When to call a technician
If the code comes back. The board is tested and repaired or replaced; ask for a diagnosis before agreeing to replace it, as it is one of the most expensive parts.

EF Outdoor DC fan motor fault Needs a technician

What it means
The fan is not turning, or it turns but the unit does not receive its rotation signal.
What you can do
Turn the unit off and check whether anything is blocking the fan: built-up dirt, a leaf or a foreign object. Never put your hand in while the power is on.
When to call a technician
If the fan turns freely but does not run. The motor, its capacitor or the board needs testing.

EH Outdoor unit suction temperature sensor fault Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

EP Compressor thermal switch fault Needs a technician

What it means
A problem running the compressor, the heart of the air conditioner.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back. Do not keep retrying, so the compressor is not damaged.

EU Voltage sensor or its connection fault Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

P0 Power module protection Needs a technician

What it means
A fault in the electronic control board or one of its parts.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Sometimes the fault is temporary after a power fluctuation.
When to call a technician
If the code comes back. The board is tested and repaired or replaced; ask for a diagnosis before agreeing to replace it, as it is one of the most expensive parts.

P1 High or low voltage protection Needs a technician

What it means
The power reaching the unit is above or below the limit, or the unit is drawing more current than allowed.
What you can do
Notice whether the lights in your home dim or flicker. Do not run the unit on an extension lead. Switch it off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code keeps appearing. The voltage is measured at the unit; the problem may be in the home's wiring or in the unit's board.

P2 Overcurrent protection Needs a technician

What it means
The power reaching the unit is above or below the limit, or the unit is drawing more current than allowed.
What you can do
Notice whether the lights in your home dim or flicker. Do not run the unit on an extension lead. Switch it off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code keeps appearing. The voltage is measured at the unit; the problem may be in the home's wiring or in the unit's board.

P4 High discharge temperature protection Needs a technician

What it means
The unit cannot reject heat outdoors fast enough, so pressure or temperature rose and it shut itself down.
What you can do
Clean the indoor unit's filter, and make sure the outdoor unit is not surrounded by obstructions and its fins are not clogged with dust. Shade it if it sits in direct sun.
When to call a technician
If the code returns even with good ventilation. The refrigerant charge may be too high or the outdoor fan weak.

P5 Overcooling protection in cooling mode Needs a technician

What it means
The air conditioner detected a fault and stopped because of it.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back after restarting.

P6 Overheating protection in cooling mode Try it yourself first

What it means
The unit cannot reject heat outdoors fast enough, so pressure or temperature rose and it shut itself down.
What you can do
Clean the indoor unit's filter, and make sure the outdoor unit is not surrounded by obstructions and its fins are not clogged with dust. Shade it if it sits in direct sun.
When to call a technician
If the code returns even with good ventilation. The refrigerant charge may be too high or the outdoor fan weak.

P7 Overheating protection in heating mode Try it yourself first

What it means
The unit cannot reject heat outdoors fast enough, so pressure or temperature rose and it shut itself down.
What you can do
Clean the indoor unit's filter, and make sure the outdoor unit is not surrounded by obstructions and its fins are not clogged with dust. Shade it if it sits in direct sun.
When to call a technician
If the code returns even with good ventilation. The refrigerant charge may be too high or the outdoor fan weak.

P8 Protection against outdoor temperature above or below the limit Not a fault

What it means
An operating status, not a fault. The unit is telling you what it is doing right now.
What you can do
Nothing. Wait until the code disappears by itself.
When to call a technician
If the code stays for hours or keeps appearing without a clear reason.

P9 Software protection of the drive circuit Needs a technician

What it means
The air conditioner detected a fault and stopped because of it.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back after restarting.