O General / Fujitsu General air conditioner error codes

32 codes, each with what it means, what you can safely try yourself, and when to call a technician.

All the codes on this page come from a single unofficial source, and we have not yet found a second one confirming them. Treat them as a first hint and check them against your appliance's manual before any repair.

A code's meaning can differ between models of the same brand. Check what you find here against your appliance's manual before any repair.

Quick table

CodeMeaningWho handles it
11Serial communication error between the indoor and outdoor unitsTry it yourself first
12Wired remote controller communication errorNeeds a technician
15Automatic airflow adjustment errorNeeds a technician
18External communication errorNeeds a technician
23Unit compatibility errorNeeds a technician
32Model information error on the indoor boardNeeds a technician
33Indoor fan motor consumption detection errorNeeds a technician
35Manual operation switch errorNeeds a technician
39Indoor fan motor power supply errorNeeds a technician
3AIndoor unit communication circuit errorNeeds a technician
41Room temperature sensor errorNeeds a technician
42Indoor heat exchanger pipe sensor errorNeeds a technician
51Indoor fan motor errorNeeds a technician
53Drain pump errorTry it yourself first
62Outdoor main board errorNeeds a technician
63Inverter errorNeeds a technician
64Active filter (PFC) circuit errorNeeds a technician
65IPM power module tripNeeds a technician
71Discharge temperature sensor errorNeeds a technician
72Compressor temperature sensor errorNeeds a technician
73Outdoor heat exchanger pipe sensor errorNeeds a technician
74Outdoor ambient temperature sensor errorNeeds a technician
84Current sensor errorNeeds a technician
86High-pressure switch errorNeeds a technician
94Overcurrent errorNeeds a technician
95Compressor motor control errorNeeds a technician
97Outdoor fan motor errorNeeds a technician
98Outdoor fan motor 2 errorNeeds a technician
99Four-way valve errorNeeds a technician
A1Discharge temperature errorNeeds a technician
A3Compressor temperature errorNeeds a technician
A5Low-pressure errorNeeds a technician

Every code explained

Everything under “What you can do” is done without opening any cover. Opening the air conditioner or measuring its wiring with the power on is a technician's job.

11 Serial communication error between the indoor and outdoor units Try it yourself first

What it means
The indoor and outdoor units (or two boards inside the unit) exchange a signal over a wire, and that signal has been lost.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Make sure the outdoor unit's breaker is on. Note whether the code started after installation, relocation or a power cut.
When to call a technician
If the code comes back after restarting. Checking the cable and terminals is done with the power on, which is a technician's job.
Note
Fujitsu General codes. The official site says they vary by model and year of manufacture

12 Wired remote controller communication error Needs a technician

What it means
The indoor and outdoor units (or two boards inside the unit) exchange a signal over a wire, and that signal has been lost.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Make sure the outdoor unit's breaker is on. Note whether the code started after installation, relocation or a power cut.
When to call a technician
If the code comes back after restarting. Checking the cable and terminals is done with the power on, which is a technician's job.

15 Automatic airflow adjustment error Needs a technician

What it means
The air conditioner detected a fault and stopped because of it.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back after restarting.

18 External communication error Needs a technician

What it means
The indoor and outdoor units (or two boards inside the unit) exchange a signal over a wire, and that signal has been lost.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Make sure the outdoor unit's breaker is on. Note whether the code started after installation, relocation or a power cut.
When to call a technician
If the code comes back after restarting. Checking the cable and terminals is done with the power on, which is a technician's job.

23 Unit compatibility error Needs a technician

What it means
The air conditioner detected a fault and stopped because of it.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back after restarting.

32 Model information error on the indoor board Needs a technician

What it means
A fault in the electronic control board or one of its parts.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Sometimes the fault is temporary after a power fluctuation.
When to call a technician
If the code comes back. The board is tested and repaired or replaced; ask for a diagnosis before agreeing to replace it, as it is one of the most expensive parts.

33 Indoor fan motor consumption detection error Needs a technician

What it means
The fan is not turning, or it turns but the unit does not receive its rotation signal.
What you can do
Turn the unit off and check whether anything is blocking the fan: built-up dirt, a leaf or a foreign object. Never put your hand in while the power is on.
When to call a technician
If the fan turns freely but does not run. The motor, its capacitor or the board needs testing.

35 Manual operation switch error Needs a technician

What it means
The air conditioner detected a fault and stopped because of it.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back after restarting.

39 Indoor fan motor power supply error Needs a technician

What it means
The fan is not turning, or it turns but the unit does not receive its rotation signal.
What you can do
Turn the unit off and check whether anything is blocking the fan: built-up dirt, a leaf or a foreign object. Never put your hand in while the power is on.
When to call a technician
If the fan turns freely but does not run. The motor, its capacitor or the board needs testing.

3A Indoor unit communication circuit error Needs a technician

What it means
The indoor and outdoor units (or two boards inside the unit) exchange a signal over a wire, and that signal has been lost.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Make sure the outdoor unit's breaker is on. Note whether the code started after installation, relocation or a power cut.
When to call a technician
If the code comes back after restarting. Checking the cable and terminals is done with the power on, which is a technician's job.

41 Room temperature sensor error Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

42 Indoor heat exchanger pipe sensor error Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

51 Indoor fan motor error Needs a technician

What it means
The fan is not turning, or it turns but the unit does not receive its rotation signal.
What you can do
Turn the unit off and check whether anything is blocking the fan: built-up dirt, a leaf or a foreign object. Never put your hand in while the power is on.
When to call a technician
If the fan turns freely but does not run. The motor, its capacitor or the board needs testing.

53 Drain pump error Try it yourself first

What it means
Condensate water isn't draining from the unit as it should, so the unit stopped itself to keep water from dripping into the room.
What you can do
Make sure the drain hose isn't kinked or blocked at its outer end, and that the indoor unit is level.
When to call a technician
If the hose looks fine from outside. An internal blockage or pump fault means opening the unit.

62 Outdoor main board error Needs a technician

What it means
A fault in the electronic control board or one of its parts.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Sometimes the fault is temporary after a power fluctuation.
When to call a technician
If the code comes back. The board is tested and repaired or replaced; ask for a diagnosis before agreeing to replace it, as it is one of the most expensive parts.

63 Inverter error Needs a technician

What it means
The air conditioner detected a fault and stopped because of it.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back after restarting.

64 Active filter (PFC) circuit error Needs a technician

What it means
A fault in the electronic control board or one of its parts.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Sometimes the fault is temporary after a power fluctuation.
When to call a technician
If the code comes back. The board is tested and repaired or replaced; ask for a diagnosis before agreeing to replace it, as it is one of the most expensive parts.

65 IPM power module trip Needs a technician

What it means
A fault in the electronic control board or one of its parts.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. Sometimes the fault is temporary after a power fluctuation.
When to call a technician
If the code comes back. The board is tested and repaired or replaced; ask for a diagnosis before agreeing to replace it, as it is one of the most expensive parts.

71 Discharge temperature sensor error Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

72 Compressor temperature sensor error Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

73 Outdoor heat exchanger pipe sensor error Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

74 Outdoor ambient temperature sensor error Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

84 Current sensor error Needs a technician

What it means
A small sensor that measures temperature or pressure somewhere in the unit is giving an illogical reading, or its wire is disconnected.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on. That is all you can do on your side.
When to call a technician
If the code comes back. The technician measures the sensor with a meter and replaces it if faulty; it is one of the simplest repairs.

86 High-pressure switch error Needs a technician

What it means
The unit cannot reject heat outdoors fast enough, so pressure or temperature rose and it shut itself down.
What you can do
Clean the indoor unit's filter, and make sure the outdoor unit is not surrounded by obstructions and its fins are not clogged with dust. Shade it if it sits in direct sun.
When to call a technician
If the code returns even with good ventilation. The refrigerant charge may be too high or the outdoor fan weak.

94 Overcurrent error Needs a technician

What it means
The power reaching the unit is above or below the limit, or the unit is drawing more current than allowed.
What you can do
Notice whether the lights in your home dim or flicker. Do not run the unit on an extension lead. Switch it off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code keeps appearing. The voltage is measured at the unit; the problem may be in the home's wiring or in the unit's board.

95 Compressor motor control error Needs a technician

What it means
A problem running the compressor, the heart of the air conditioner.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back. Do not keep retrying, so the compressor is not damaged.

97 Outdoor fan motor error Needs a technician

What it means
The fan is not turning, or it turns but the unit does not receive its rotation signal.
What you can do
Turn the unit off and check whether anything is blocking the fan: built-up dirt, a leaf or a foreign object. Never put your hand in while the power is on.
When to call a technician
If the fan turns freely but does not run. The motor, its capacitor or the board needs testing.

98 Outdoor fan motor 2 error Needs a technician

What it means
The fan is not turning, or it turns but the unit does not receive its rotation signal.
What you can do
Turn the unit off and check whether anything is blocking the fan: built-up dirt, a leaf or a foreign object. Never put your hand in while the power is on.
When to call a technician
If the fan turns freely but does not run. The motor, its capacitor or the board needs testing.

99 Four-way valve error Needs a technician

What it means
The valve that switches the unit between cooling and heating isn't changing over.
What you can do
Try switching between cooling and heating once after restarting.
When to call a technician
If the code stays. The valve or its coil needs checking.

A1 Discharge temperature error Needs a technician

What it means
The air conditioner detected a fault and stopped because of it.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back after restarting.

A3 Compressor temperature error Needs a technician

What it means
A problem running the compressor, the heart of the air conditioner.
What you can do
Switch the air conditioner off at the breaker for five minutes, then turn it back on.
When to call a technician
If the code comes back. Do not keep retrying, so the compressor is not damaged.

A5 Low-pressure error Needs a technician

What it means
There is less refrigerant in the system than needed, usually because of a leak.
What you can do
Clean the filter and confirm that cooling really is weak. There is nothing else to do on your side.
When to call a technician
In almost every case. Ask the technician to find and repair the leak before recharging; recharging alone is only a temporary fix.